Thursday, May 23, 2013
|
|
|
 |

ProfiTrace 2 is the most powerful mobile analyzer for PROFIBUS networks. It is the latest generation in the line of busmonitor technology. Thousands of users benefit daily from this great tool. ProfiTrace combines all required tools in one:
Busmonitor
Oscilloscope
Bar graph
Topology Scan
Reporting
DP Master
Technicians can check and troubleshoot the complete PROFIBUS network with 1 software package and 1 piece of hardware. This is an enormous reduction in equipment, weight, costs and required knowledge. The advanced USB hardware (ProfiCore™ Ultra) is internally equipped with a high-speed digital oscilloscope and able to capture bus signals running at 12 Mbps.
ProfiTrace is an essential tool for maintenance, commissioning and troubleshooting as well as product development. Typical failures such as noise, reflections, voltage drops, termination problems, double addresses, wire breaks and configuration faults are easily identified. Random errors such as overshoots, error telegrams, repeats and diagnostics can also be captured and logged. The results can be exported to detailed reports which are accepted by the industry. Predictive maintenance and asset management are really possible with ProfiTrace! This outstanding tool that fits in your pocket, will boost the capabilities of service, maintenance and engineering technicians.
 |
 |
Busmonitor for DP and PA with powerful statistics
Repeats, fall-outs, corrupted messages, diagnostics, cycle time, etc. |
 |
High-speed digital oscilloscope - ScopeWare
Differential voltage, A-line, B-line, noise, overshoots, reflections, triggers. |
 |
Bar graph
Average, Min. and Max. values of the bus signals per device. |
 |
Topology Scan
Automatic generation of the network topology. |
 |
Reporting
Automatic generation of detailed reports that are accepted by the industry. |
 |
DP master - ProfiCaptain
A complete DP master has been integrated (V0 and V1). |
 |
ProfiCore Ultra USB interface
Useable on PC platforms, no power supply required and elimination of spur lines. |
 |
OPC server and CommDTM |
 |
XP, Vista and Windows 7 platforms |
 |
Multi language user interface |
| |
 |
 |
Troubleshooting & maintenance of PROFIBUS networks
(ProfiTrace, ScopeWare, Topology scan and ProfiCaptain) |
 |
Commissioning of PROFIBUS networks
(ProfiTrace, ScopeWare, Topology scan and ProfiCaptain) |
 |
PROFIBUS product testing and verification
(ProfiTrace, ScopeWare, ProfiCaptain and CommDTM) |
 |
Passive cable testing
(ScopeWare and ProfiCaptain) |
 |
I/O testing of PROFIBUS devices
(ProfiCaptain) |
 |
Setting up and diagnose PROFIBUS devices
(CommDTM) |
 |
Address setting of PROFIBUS devices
(ProfiCaptain) |
 |
Interface for bus statistics and device I/O to external apps
(OPC server) |
 |
Education |
| |
 |

 |
 |
"Colours make it easy….."
The Live List is a matrix that continuously lists all the available devices. It is directly visible which devices are ‘troublemakers’.
With different background colours the status of the devices is displayed;
- Green: Device is in Data Exchange
- Yellow: Device is lost
- Red: Parameter fault
- Purple: Configuration fault
- No colour: Not in Data Exchange
The Live List can also generate the product name of the devices when a diagnostic message is captured (synchronized with the GSD library).
 |
"Click and go….."
The statistics matrix is the most powerful feature of the analyzer. This field can really indicate what the condition of the installation is. It displays all the important information that a user, especially a maintenance technician is really interested in;
Retry messages
Fall-outs
Bus cycle time
Diagnostic messages, etc.
Because of this feature, the user does not have to inspect messages or do difficult operations to ensure the quality of the installation.
If the statistics do NOT show deviations, the installation is on the 1st degree OK!!!
 |
"The absolute truth....."
When the user records messages, he has a perfect visual representation on the screen;
Visualization of FDL, DP, DP-V1, DP-V2, PA and I&M messages.
Messages can be filtered and stored.
Data interpretation of bytes, words, floating points, etc.
Error detection.
Bookmarks.
 |
 |

 |

 |
 |
"The easiest oscilloscope ever....."
With the built in oscilloscope we can detect; noise, reflections, termination problems, etc.
Time scale: 50 ns to 500 ms.
Voltage scale: 0,5 to 5 V per DIV.
Cursors (voltage and time).
Differential (B-A) and single ended (A and/or B line) measurements.
Trigger per device or free running.
Trigger features: start of response, request message and voltage level.
Bit interpretation engine.
 |

 |
 |
All features of ScopeWare DP.
Max. 33 V DC.
Max. 1,2 Vtt AC.
AC and DC can be displayed simultaneously.
Detects missing termination.
PA Probe Ultra is required.
 |

 |
 |
The bar graph is a helpful utility to get an impression of the overall signal quality of the network.
2 Selectable modes: Average signal level and minimum difference between 1 and 0.
Average, min. and max. signal level indicator.
Colours state the quality of the signals.
Can be sorted on: address and Voltage.
Continuously updated.
 |
Automatic generation of the network topology.
No shutdown required!
No disturbance in the cycle time!
Works on 500 kbps and 1,5 Mbps.
On passive networks in conjunction with ProfiCaptain.
 |
 |

 |
"We have proof….."
The reporting feature creates a detailed report that contains the signals of all devices, their faults, the network topology, bar graph and administrative information.
Generation of detailed network reports.
Address list with manufacturer information.
Oscilloscope images of every device.
Live List, Bar graph and Topology structure.
Summary of detected errors.
Standard layout for signatures and approvals.
Import of company logo.
 |
 |

 |
"Test and control your devices....."
Complete integration of ProfiCaptain.
Putting slaves in Data Exchange.
I/O control with automatic patterns.
Automatic detection of existing busparameters.
Brand new concept of 'stealing' slaves.
Class 2 functions in a Class 1 framework.
No shutdowns when updating the configuration.
Deactivating slaves in the configuration.
 |
 |

 |
PROFIBUS
12 Mbps (all baudrates)
Galvanic isolated PROFIBUS interface
Latest RS 485 technology
Oscilloscope
Frequency: 2 x 192 MHz
Bandwidth: 100 MHz
Differential measurement: -9..+9 V
Single ended: -4,5..+8 V
Others
High-speed USB 2.0 interface
External power supply possible if required
 |
|
| |
|
 |
|
|
|
|
 |